318
Explicit Messages Appendix A
Maximum
Value Read
Read/
Reset
Reads the maximum
value after power is
turned ON.
Read:
0E hex
Reset:
35 hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
7C hex 4 bytes
Minimum
Value Read
Read/
Reset
Reads the minimum
value after power is
turned ON.
Read:
0E hex
Reset:
35 hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
7D hex 4 bytes
Peak Value
Read
Read The peak value while
the hold function is
operating is held and
the peak value is read.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
7E hex 4 bytes
Bottom
Value Read
Read The bottom value while
the hold function is
operating is held and
the bottom value is
read.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
7F hex 4 bytes
Top Value
Read
Read The top value while the
hold function is operat-
ing is held and the top
value is read.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
80 hex 4 bytes
Top Detec-
tion Timing
Flag Read
Read Reads the timing for
detecting top values.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
81 hex 1 byte
Valley
Value Read
Read The valley value while
the hold function is
operating is held and
the valley value is read.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
82 hex 4 bytes
Valley
Detection
Timing Flag
Read
Read Reads the timing for
detecting valley values.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
83 hex 1 byte
HH Value
Setting
Write/
Read
Sets the HH value. Write:
10 hex
Read:
0E hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
6D hex 4 bytes
(415000 to
415000)
4bytes
(415000 to
415000)
LL Value
Setting
Write/
Read
Sets the LL value. Write:
10 hex
Read:
0E hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
6E hex 4 bytes
(415000 to
415000)
4bytes
(415000 to
415000)
H Value
Setting
Write/
Read
Sets the H value. Write:
10 hex
Read:
0E hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
6F hex 4 bytes
(415000 to
415000)
4bytes
(415000 to
415000)
L Value
Setting
Write/
Read
Sets the L value. Write:
10 hex
Read:
0E hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
70 hex 4 bytes
(415000 to
415000)
4bytes
(415000 to
415000)
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data

Table of Contents