326
Explicit Messages Appendix A
Action on
Rising Edge
of Digital
Input
Read Reads the action
performed on the
rising edge of the
digital input.
0E hex 8E hex 01 to 40
hex
*1
91 hex --- 1 byte
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
Write Writes the action
performed on the
rising edge of the
digital input.
10 hex 8E hex 01 to 40
hex
*1
91 hex 1 byte
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
---
Action on
Falling Edge
of Digital
Input
Read Reads the action
performed on the
falling edge of the
digital input.
0E hex 8E hex 01 to 40
hex
*1
92 hex --- 1 byte
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
Write Writes the action
performed on the
falling edge of the
digital input.
10 hex 8E hex 01 to 40
hex
*1
92 hex 1 byte
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
---
Action on
Bus Error
Read Reads the action
performed when
a bus error
occurs.
The same setting
applies to all out-
puts.
0E hex 8E hex 01 to 40
hex
*1
93 hex --- 1 byte
00 hex: Outputs
are cleared on bus
error.
01 hex: Output
functionality is
maintained on bus
error.
Write Writes the action
performed when
a bus error
occurs.
The same setting
applies to all out-
puts.
10 hex 8E hex 01 to 40
hex
*1
93 hex 1 byte
00 hex: Outputs
are cleared on
bus error.
01 hex: Output
functionality is
maintained on
bus error.
---
Configura-
tion Tag
Read Reads the
present value of
the configuration
tag.
0E hex 8E hex 01 to 40
hex
*1
94 hex --- 1 byte
Range of values:
00 to FF hex
(0 to 255 decimal)
Write Writes the value
of the configura-
tion tag.
10 hex 8E hex 01 to 40
hex
*1
94 hex 1 byte
Range of values:
00 to FF hex
(0 to 255 decimal)
---
Range 0 Write Writes the upper
and lower limits of
range 0.
*3
33 hex 8E hex 01 to 40
hex
*1
95 hex 2 × 4 bytes
Range of values:
8000 0000 to
7FFF FFFF hex
(-2,147,483,648
to 2,147,483,647
decimal)
*4
---
Save
Ranges and
Preset Val-
ues
Write Writes the range
settings and pre-
set value to non-
volatile memory.
10 hex 8E hex 01 to 40
hex
*1
97 hex 1 byte
Value: 00 hex
---
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size