Constant
no.
SettingSetting rangeDescriptionIndi-
cators
n22 Acceleration
time 2
0.0 to 999 (seconds) [10.0]
n23 Deceleration
time 2
0.0 to 999 (seconds) [10.0]
n24 Maximum
frequency
50.0 to 400 (Hz) [60.0]
n25 Maximum
voltage
1 to 255 (V) [200]
n26 Maximum
voltage
frequency (basic
frequency)
1.6 to 400 (Hz) [60.0]
n31 Electronic
thermal
reference
current
0.0 to 120% of rated Inverter amperage
Specify the rated motor amperage.
n33 Stall prevention
0: Stall prevention
ur
ng
deceleration
1: No stall prevention
n36 Operation after
0: Discontinues operation.
recovery from
power
1: Continues operation only if the power
interruption is within 0.5 second.
interruption
2: Continues operation unconditionally.
n37 Carrier
1: 2.5 (kHz)
frequency
2: 5 (kHz)
3: 7.5 (kHz)
4: 10 (kHz)