EasyManuals Logo

Onicon D-100 User Manual

Onicon D-100
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
1500 North Belcher Road, Clearwater, FL 33765 Tel (727) 447-6140 • Fax (727) 442-5699 sales@onicon.com
D-100 Flow Display Manual 08-12 - 0634-7 Page 25
SECTION 5.0: DIAGNOSTICS
5.1 DIAGNOSTICS
The ONICON D-100 display is programmable. Factory programmed settings provide rate and
total values in accordance with the customer’s application data. Refer to the D-100 calibration
sheet for a complete listing of factory settings. These settings may be reviewed and changed with
assistance from ONICON factory service personnel. The display is also equipped with diagnostic
indicator lights and self diagnostic test signals that conrm the operation of the microprocessor
and its input circuitry. Please contact the ONICON factory service personnel if any of the
diagnostic lights or test signals listed below indicates a potential problem with the operation of
the Btu meter.
5.1.1 Diagnostic Lights
LowVoltagePowerSupply
Located on the power supply board inside the System-10 BTU Meter (refer to page A-3),
these two LEDs will be illuminated when the positive and negative ve volt supplies
are present.
Liquid Flow
Locatedjustabovethepowersupplyonthemotherboard(refertopageA-1)istheow
indicator LED. The LED will ash at a rate that is proportional to the liquid ow rate.
An unlit LED indicates no ow signal.
5.1.2 Flow Test Signals
Located on the right side of the motherboard (refer to A-1) immediately above the power
supply board is a three position slide switch used to test the ow input. When the switch
is in the top position, the input is connected to the ow meter. When the switch is in the
middle position, the input is connected to two test terminals used to apply a variable
frequency to simulate ow. When the switch is in the bottom position, the input is
connected to a 50/60 Hz signal that simulates a xed ow rate. Refer to the calibration
certicate to determine the correct display reading when operating in the 50/60 Hz test
mode.
5.1.3 Ai3 & Ai4 Test Signals
As you are facing the component side of the processor board, the Ai3/Ai4 Test push button
isalongthetopedgeoftheboardjusttotheleftoftheatribboncable.ItislabeledTEMP
TEST. When pressed, a xed current will be applied to each sensor input. Both Ai3 and
Ai4 will produce an output equal to 37.5% of their programmed full scale output. This test
conrms the operation of the D-100 processor board input circuitry for Ai3 and Ai4.
IMPORTANT NOTE
The second line of the display will alternate between TEST MODE and the normal display of
engineering units and multipliers whenever the ow test switch is in the TEST or 60 Hz positions.
i
IMPORTANT NOTE
After operating for ve minutes in either the TEST or 60 Hz mode, the displayed ow and energy
rate will be disabled, and the meter will report a zero ow rate and a zero energy rate to the
network. The meter will remain in this state until the switch is set to RUN.
i

Table of Contents

Other manuals for Onicon D-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Onicon D-100 and is the answer not in the manual?

Onicon D-100 Specifications

General IconGeneral
BrandOnicon
ModelD-100
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals