EasyManua.ls Logo

Onicon D-100 - SECTION 3.0: NETWORK TROUBLESHOOTING TIPS; 3.1 Troubleshooting

Onicon D-100
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1500 North Belcher Road, Clearwater, FL 33765 Tel (727) 447-6140 • Fax (727) 442-5699 sales@onicon.com
D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2 Page 23
3.1 TROUBLESHOOTING
Reported Problem Possible Solutions
Device will not communicate with the
network controller.
• IsthereceiveLEDashingonthenetwork
board? This LED will ash whenever there
is trafc on the network. If the LED is not
ashing, look for an open network cable.
• IsthetransmitLEDashing?The
transmit LED will only ash when the
device is responding to a poll. A unique
address is required for each device on
the network. Duplicate addresses will
cause some or all of the devices on the
network to quit working. (See section
1.6.1 of this manual for details.)
• TheRS485networkcableconnectionsare
polarity sensitive and must be connected
the same way on every device (i.e. + to +
and - to -). (See section 1.4.1 of this
manual for details.)
• TheBaudratesettingmustmatchthe
network Baud rate. (See section 1.5.1 of
this manual for details.)
• Shielddrainconnectionsshouldbedaisy
chained in the same manner as the
signal cables for RS485. The shield drain
wire should be left unterminated at the
end of the cable and connected to earth
only at the network master controller.
Shield wires must not be connected to the
RS485 connector on the D-100.
• Themaximumnumberofdevicesallowed
on an RS485 network segment without a
repeater is 32. Adding more than 32
devices to a single segment may reduce
the transceiver output voltage to a level
that is too low to be distinguished from
background noise on the cable.
SECTION 3.0: NETWORK TROUBLESHOOTING TIPS

Table of Contents

Other manuals for Onicon D-100

Related product manuals