No. SX-DSV02472 -100-
6-4 Torque saturation protection function
If torque saturated has continued for a fixed period, an alarm can be activated.
Parameters
Class No.
At-
trib-
Title Range Unit Function
7 16 B
Frequency of torque
saturation protection
0–30000
time
If
torque saturated is continued during a preset frequency, Err 16.1
“
Torque saturation protection” will be activated.
If the setup value is 0, this function is disabled and Err 16.1 will not be
• For the frequency, the count increases by one for every 0.25ms.
For example if the frequency is set to 30000, Err16.1 will be activated if torque saturated has continued
for about 7.5 seconds.
• When torque is controlled, this function is disabled and Err 16.1 will not be activated.
• If the immediate stop alarm is activated, this function is disabled and Err 16.1 will not be activated.
Torque command
Torque in-limit signal output
Err16.1 will not be activated if
thrust saturated has not
continued for Pr7.16 setup
value0.25ms, and count will
be cleared.
Err16.1 will be activated if
thrust saturated has continued
for Pr7.16 setup value0.25ms.
Err16.1 is issued
Pr7.16 Setup value0.25ms Pr7.16 Setup value0.25ms or lower
OFF
OFF ON
ON
issued
Time
Torque
Torque limit