EasyManua.ls Logo

Panasonic MINAS-A5B Series - Setting Regenerative Resistor

Panasonic MINAS-A5B Series
155 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. SX-DSV02472 -44-
4-6 Setting regenerative resistor
The table describes setup of regenerative resistor.
For details of regenerative resistor specification, refer to Technical Reference SX-DSV02201.
Parameters
Class No.
At-
trib-
ute *1)
Title Range Unit Function
0 16 C
External
Regenerative
resistor setup
0–3
With this parameter, you can select either to use the built-in
regenerative resistor of the driver, or to separate this built-in
regenerative resistor and externally install the regenerative resistor.
0: Use the built-in resistor and activate regenerative over-load
protection.
1: Use the external resistor and activate regenerative over-load
protection.
2: Use the external resistor but do not activate regenerative
over-load protection.
3: Do not use regenerative resistor. (Do not use over-load
protection.)
0 17 C
Selection of load
factor of external
regenerative
resistor
0–4
When selecting the external regenerative resistor (Pr 0.16 = 1, 2),
select the computing method of load factor of regenerative resistor.
0: Regenerative load factor is 100% when duty factor of external
regenerative resistor is 10%. (Compatible with A4N series)
1–4: For manufacturers use (do not setup)
*1) For parameter attribute, refer to Section 9-1.
R1.05
Motor Business Division, Appliances Company, Panasonic Corporation

Table of Contents