3-4 Monitor signal output function
2 types of analog signals can be output for monitoring from the analog monitor connectors (X7) in the front panel.
Types of monitor and scaling (output gain setting) can be set by the parameters below.
■ Parameters
Class No.
At-
trib-
Title Range Unit Function
4 16 A
Type of analog
0–24 —
Select the type of monitor for analog monitor 1.
4 17 A
Analog monitor
1 output gain
0–214748364
[Monitor
unit in
Pr 4.16] /
Set up the output gain of analog monitor 1.
For Pr 4.16 = 0 Motor velocity,
1 V is output at the motor velocity [r/min] = Pr 4.17 setup value.
4 18 A
Type of analog
0–24 —
Select the type of monitor for analog monitor 2.
4 19 A
Analog monitor
2 output gain
0–214748364
[Monitor
unit in
Pr 4.18] /
Set up the output gain of analog monitor 2.
For Pr 4.18 = 4 Torque command,
1 V is output at the torque command [%] = Pr 4.19 setup value.
4 21 A
Analog monitor
output setup
0–2 —
Select output format of the analog monitor.
0: Signed data output –10 V to 10 V
1: Absolute value data output 0 V to 10 V
2: Data output with offset 0 V to 10 V (5 V at center)
*1) Refer to Section 9-1 for parameter attribute.
(1) Pr 4.21 Analog monitor output setup:
Figure below shows output specification when Pr 4.21 is 0, 1 or 2.
speed
[r/min]
Pr 4.21 = 0, signed data output
(output range −10 to 10 V)
speed
[r/min]
Pr 4.21 = 1, absolute value data output
(output range 0 to 10 V)
speed
[r/min]
Pr 4.21 = 2, data output with offset
(output range 0 to 10 V)
• When monitor type is motor speed, and conversion gain is 500 (1 V = 500 r/min).