13
Chapter 1
System Outline
The main line is the longest route distributed from the controller.
The branch lines are the routes branched from the main line.
NOTE
The total cable length should satisfy the conditions shown in the following table:
Transmission mode Total cable length (m)
A 100
B 400
C 1,600
The maximum transmission distance (between D and G) will be as follows:
A mode: 50m
The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm
2
) and the number
of nodes (1 to 256 nodes).
B mode
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 224 nodes
Up to 256
nodes
0.3 180
0.5
200 (full specication for B mode)
0.75
1.25
2.0
C mode
Conductor
cross
section
(mm
2
)
Number of nodes and maximum transmission length (m)
Up to 32
nodes
Up to 64
nodes
Up to 96
nodes
Up to 128
nodes
Up to 160
nodes
Up to 192
nodes
Up to 224
nodes
Up to256
nodes
0.3 570 440 350 300 260 220 200 180
0.5 710 580 490 420 370 330 300
0.75 780 670 590 530 480
1.25
800 (full specication for C mode)
2.0
Voltage drop between +24V and 0V is not considered. For this reason, calculate this volt-
age drop value, and use a local power supply unit, etc. For a detailed description, refer to
the ‘S-LINK V Users Manual.’
The conductor cross section of the exclusive 4-core at cable (SL-RCM□) is 0.5mm
2
.
Wire the S-LINK V system while observing the transmission distance specications de-
scribed above. In addition, use the cables that satisfy the specications described above.
To select applicable cables, refer to the ‘S-LINK V Users Manual.’
NOTE