Chapter 3
Cable Connection
Cautions
Process and tighten the wires as follows:
Lead wire
Loosens
Tightens
A
<Dimension A>
S-LINK V terminal block connector side : 7mm
DeviceNet terminal block connector side: 7mm
<Tightening torque>
S-LINK V terminal block connector side : 0.5N·m or less
DeviceNet terminal block connector side: 0.6N·m or less
Recommended tool: Small-sized flathead screwdriver
S-LINK V terminal block connector side:
Width = 3.8mm or less, thickness = 0.7mm or less
DeviceNet terminal block connector side:
Width = 4mm or less, thickness = 0.7mm or less
Wire processing dimension
Take care that wrong wiring will damage the product.
Do not short-circuit ‘0V’ and ‘G’ on the S-LINK V terminal block connector side.
A large current may ow through the external power supply input, depending on the load. Use wires having
sufcient current capacity. Further, when supplying power to the load from SL-VGU1-D, make sure not to ex-
ceed the allowable through current.
Tighten the screws of the ange also, so that the terminal block on the S-LINK V terminal block connector
side does not come out. The tightening torque should be 0.5N·m, or less.
Do not apply solder, etc., on the tips of the wires to be connected to the terminal block. This can cause loos-
ening of the screws, resulting in wire disconnection.