Chapter 2
Cable Connection
Cautions
Process and tighten the wires as follows:
Lead wire
Loosens
Tightens
A
<Dimension A>
S-LINK V terminal block connector side : 7mm
CC-Link terminal block connector side : 6mm
<Tightening torque>
S-LINK V terminal block connector side : 0.5N·m or less
CC-Link terminal block connector side : 0.2N·m or less
Recommended tool: Small-sized flathead screwdriver
S-LINK V terminal block connector side:
Width = 3.8mm or less, thickness = 0.7mm or less
CC-link terminal block connector side:
Width = 2.5mm or less, thickness = 0.5mm or less
Wire processing dimension
Take care that wrong wiring will damage the product.
Do not short-circuit ‘0V’ and ‘G’ on the S-LINK V terminal block connector side.
A large current may ow through the external power supply input, depending on the load. Use wires having
sufcient current capacity. Further, when supplying power to the load from SL-VGU1-C, make sure not to ex-
ceed the allowable through current.
Tighten the screws of the ange also, so that the terminal block does not come out. The tightening torque
should be 0.5N·m, or less, on the S-LINK V terminal block connector side and 0.2N·m, or less, on the CC-
Link terminal block connector side.
Do not apply solder, etc., on the tips of the wires to be connected to the terminal block. This can cause loos-
ening of the screws, resulting in wire disconnection.
The F.G. terminal on the S-LINK V terminal block connector and the S terminal on the CC-Link terminal block
connector are not connected. When grounding, ground them separately.