54
Chapter 2
Starting
Setting of CC-Link Side and S-LINK V System Side
Setting example
The CC-Link master setting example and the SL-VGU1-C setting example are shown below.
Each item is set under the conditions shown in the following gure:
Station number: 0
SL-VGU1-C
Station number: 1
4 stations occupied
SL-VGU1-C
Station number: 5
4 stations occupied
Setting item 1st controller 2nd controller
Master unit
Station number setting 0 (Be sure to set the station number to '0' for the master.)
Mode setting 0: Online (Data linking and automatic multi-line scanning are possible.)
Transmission speed setting 0: 156kbps
SL-VGU1-C
Station number setting 01 (X10: 0, X1: 1) 05 (X10: 0, X1: 5)
Transmission speed setting 0: 156kbps
Buffer memory assignment Remote I/O Remote register
Setting of transmission mode A mode
I/O control points setting 256 points 512 points
I/O setting
Input: 128 points, Output: 128 points Input: 256 points, Output: 256 points
Input address: 0 to 127
Output address: 128 to 255
Input address: 0 to 255
Output address: 256 to 511
Error outputting operation setting Output of all errors: Errors 1 to 5
Decimal / hexadecimal number display setting Decimal number display mode
Output hold / clear Output hold
1. Master unit station number setting (rotary switch)
Rotary switch: ‘00’ Station number ‘0’ (Be sure to set the station number to ‘0’ for the master station.)
2. Master unit mode setting (rotary switch)
Rotary switch: ‘0’ Online (Data linking and automatic multi-line scanning are possible.)
3. Master unit transmission speed setting (rotary switch)
Rotary switch: ‘0’ 156kbps
4. Master unit condition setting (DIP switches)
Set the DIP switches considering the conditions.
5. SL-VGU1-C station number setting (rotary switch)
Rotary switch: ‘01’ and ‘05’
6. SL-VGU1-C transmission speed setting (rotary switch)
Rotary switch: ‘0’ 156kbps