87
Chapter 3
Starting
Setting of DeviceNet side or S-LINK V system side
Setting of DeviceNet side
DeviceNet address setting switches (MAC ID)
Use these switches to set the addresses on the DeviceNet.
54321
MAC ID 32 16 8 4 2 1
0 OFF OFF OFF OFF OFF OFF
1 OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF ON ON
···
···
···
···
···
···
···
62 ON ON ON ON ON OFF
63 ON ON ON ON ON ON
DeviceNet transmission speed setting switches (Baud Rate)
Use these switches to set the transmission speed (Baud Rate) of the DeviceNet.
Set the same values as the master side.
54321
Transmission speed 1 0
125kbps OFF OFF
250kbps OFF ON
500kbps ON OFF
Not used ON ON
Setting of S-LINK V system side
1. Set the mode selection switch to CONFIG, and then turn on the power.
2. Various setting items will be displayed. Set these items considering the system conditions.
3. For a detailed description of setting, refer to page 80 ‘CONFIG Mode.’
Output hold
If data exchange with the master station is disabled during transmission monitoring operation, the output con-
dition of the S-LINK V output unit can be held or cleared. Set whether the output condition should be held or
cleared.
Output of S-LINK V output unit
Output hold Holds the output condition.
Output clear Turns off the output.
Note: If an error (error 1 or 2) occurs on the S-LINK V system side, the output condition of the S-LINK V output unit will be held or cleared
depending on the set position of the output hold setting switch.