30
Chapter 2
Functional Description
No. Designation Description
3 ENTER key
When the ENTER key is pressed, the setting value of each setting is entered.
When system set is displayed, if ENTER key is pressed for 3 sec., or more, system set is performed.
4 SELECT keys
They are used to change the displayed item or setting item, and to change the numerical value of each
setting.
5 Mode selection switch It is used to change to RUN / CHECK / CONFIG modes.
6
Transmission indicator
(Green)
It blinks during transmission (signal generation). The frequency of blinking differs depending on the
transmission mode.
7 Error indicator (Red)
It shows the error condition.
Lights up: Error occurrence
• Blinks: Cause rectied after error occurrence (error record).
8
S-LINK V terminal block
connector
+24V, 0V and F.G. are supplied from the external power supply, and +24V, 0V, D and G are supplied to I/
O units. Further, the error output is connected to the external device.
9
Operation
indicators
L RUN
(Green)
It indicates whether data transmission is being carried out normally between SL-VGU1-C and the master
station.
Lights up: When the correct data is received from the master station.
Turns off: When there is error in data receiving or transmission (CRC error), or when time-over occurs.
(However, lights up when the correct data is received.)
L ERROR
(Red)
Lights up: When transmission error (CRC error) occurs or when there is a mistake in station No. / trans-
mission speed setting. (However, turns off when setting is rectified and power supply is
switched on again.)
Blinks: When station No. setting / transmission speed setting is changed in-between
Turns off: When transmission error (CRC error) or time-over occurs
RD (Green) Lights up when data is received.
SD (Green) Lights up when data is transmitted.
10
Station No. setting switches
(ST.NO)
Make sure to set the station No. of SL-VGU1-C from 01 to 64.
'x10' sets the tens position of the station No.
'x1' sets the ones position of the station No.
(The occupied station No. changes depending on S-LINK V I/O control No.)
11
Transmission speed set-
ting switch (B RATE)
It sets the transmission speed of CC-Link.
Setting Transmission speed
0 156kbps
1 625kbps
2 2.5Mbps
3 5Mbps
4 10Mbps
Make sure to set the transmission speed setting switch in the range of 0 to 4.
12
CC-Link terminal block
connector
It is the terminal block connector for connection of CC-Link transmission signal.