74
Chapter 3
Functional Description
No. Designation Description
3 ENTER key
●When ENTER key is pressed, the setting value of each setting is entered.
●When system set is displayed, if ENTER key is pressed for 3 sec., or more, system set is performed.
4 SELECT keys
●They are used to change the displayed item or setting item, and to change the numerical value of each
setting.
5 Mode selection switch ● It is used to change to RUN / CHECK / CONFIG modes.
6
Transmission indicator
(Green)
●It blinks during transmission (signal generation). The frequency of blinking differs depending on the
transmission mode.
7 Error indicator (Red)
●It shows the error condition.
• Lights up: Error occurrence
• Blinks: Cause rectied after error occurrence (error record).
8
S-LINK V terminal block
connector
●+24V, 0V, and F.G. are supplied from the external power supply, and +24V, 0V, D, and G are supplied to
I/O units. Further, the error output is connected to the external device.
9
DeviceNet
indicators
Network
Status
(Green, Red)
●Lights up in green: When transmission connection is complete
●Blinks in green: When setting is incomplete
●Lights up in red: During a serious transmission error
●Blinks in red: During a minor transmission error
●Turns off: When power supply is OFF, or when power supply is ON in CONFIG mode
Module
Network Status
(Green, Red)
●Lights up in green: During normal operation
●Lights up in red: During a serious transmission error
●Blinks in red: During wait state
●Turns off: When power supply is OFF, or when power supply is ON in CONFIG mode
10
DeviceNet address setting
switches (MAC ID)
●It is used to set the MAC ID of DeviceNet.
●Make sure to set the MAC ID of SL-VGU1-D in the range of 00 to 63.
11
DeviceNet
transmisson speed
setting switches
(Baud Rate)
●It sets the transmission speed of DeviceNet.
Transmission speed 1 0
125kbps OFF OFF
250kbps OFF ON
500kbps ON OFF
Not used ON ON
12
DeviceNet terminal block
connector
●It is the terminal block connector for connection of DeviceNet transmission signal.