AS-i 3.0 EtherNet/IP+Modbus TCP Gateway
The Modbus Address Table
26.9.2013
75
11.3 AS-i circuit 1 analog data
11.3.1 16 bit output data of AS-i slaves according to slave profile 7.3 or 7.4
11.3.2 16 bit input data of AS-i slaves according to slave profile 7.3 or 7.4
Information!
B addresses are located behind A addresses.
Addresses 0 31 correspond to 0A 31A, addresses 32 64 correspond to
0B 31B.
AS-i circuit 1
16 bit output data of AS-i slaves according to slave profile 7.3 or 7.4
data
4x
reference
word
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
5125 1 slave at address 1, channel 1
5126 2 slave at address 1, channel 2
... ...
5248 124 slave at address 31, channel 4
Tab. 11-53.
AS-i circuit 1
16 bit input data of AS-i slaves according to slave profile 7.3 or 7.4
data
4x
reference
word
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
5253 1 slave at address 1, channel 1
5254 2 slave at address 1, channel 2
... ...
5376 124 slave at address 31, channel 4
Tab. 11-54.