10.6 AS-i slave Object
class code: 101 (0x65)
64 instances for each AS-i circuit, 1 for each AS-i slave
instance ID AS-i slave
1 (0x01) slave 0, circuit 1
2 (0x02) slave 1A, circuit 1
……
32 (0x20) slave 31A circuit 1
33 (0x21) empty, circuit 1
34 (0x22) slave 1B, circuit
……
64 (0x40) slave 31B, circuit 1
65 (0x41) slave 0, circuit 2
……
96 (0x60) slave 31A, circuit 2
97 (0x61) empty, circuit 2
……
98 (0x62) slave 1B, circuit 2
……
128 (0x80) slave 31B, circuit 2
Tab. 10-17.
attribute
ID
access
rule
name devicenet
data type
remark
100 (0x64) get actual configuration UINT
101 (0x65) get/set permanent configuration UINT slave 0, 32: not read-/writea-
ble
102 (0x66) get/set actual parameters USINT
103 (0x67) get/set permanent parameters USINT
104 (0x68) get/set xID1 USINT slave 0: writeable only,
slave 0 - 32: readable
Tab. 10-18.
actual configuration/permanent configuration (16-bit)
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
ID IO xID2 XID1
Tab. 10-19.
parameter xID1 (8-bit)
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
–data
Tab. 10-20.