KENR6933 33
Troubleshooting Section
Table 21
Minimum Maximum
Default
0 rpm 3000 rpm 0 rpm
Throttle Lock Increment Speed Ramp
Rate
The “Throttle Lock Increment Speed Ramp Rate”
is the rate of engine acceleration when the PTO
switch is held in the ACCELERATE position. If this
parameter is set to “0”, the feature is turned off.
Table 22
Minimum Maximum Default
0 rpm/sec 600 rpm/sec 400 rpm/sec
Throttle Lock Engine Set Speed
Increment
The “Throttle Lock Engine Set Speed Increment”
controls the increase in engine speed when the
PTO switch is briefly operated to ACCELERATE or
DECELERATE. If this parameter is set to “0”, the
feature is turned off.
Table 23
Minimum Maximum
Default
0 rpm 200 rpm 10 rpm
Miscellaneo
us
Monitoring Mode Shutdowns
“Monitoring Mode Shutdowns” controls the shutdown
feature that is associated with the engine monitoring
feature. Wh
en this feature is enabled and an event
code with a “-3” suffix is detected, the engine will be
shut down.
Table 24
Value Default
Disabled
Enabled
Disabled
Monitoring Mode Derates
“Monitoring Mode Derates” controls the derate that is
associated with the engine monitoring feature. When
this feature is enabled and an event code with a “-2”
is detected, the engine will be derated.
Table 25
Value
Default
Disabled
Enabled
Enabled
Limp Home Desired Engine Speed
The “Limp Home Desired Engine Speed” is the
maximum speed of the engine when the engine has
been derated.
Table 26
Minimum Maximum Default
700 rpm 1800 rpm 1200 rpm
J1939 Continuous Fault Handling
Remote Torque Speed Control Enable
Status
The “Remote Torque Speed Control Enable Status”
parameter determines the way that faults w ill be
handled by the ECM when the “J1939 Torque Speed
Control (TSC1)” message is used as a speed request
input to the ECM. Programming the “Remote Torque
Speed Control Enable Status” to “Enabled” will cause
the ECM to display a fault code if a valid TSC1
message is not received by the engine ECM within
30 seconds of the engine starting. If the“ Remote
Torque Speed Control Enable Status” is programmed
to “Disabled”, the engine will display a 247-12 Data
Link malfunction immediately after a loss of a TSC1
message. Program “Remote Torque Speed Control
Enable Status” to “Enabled” if the ECM will always be
receivingaTSC1message.
Table 27
Value Default
Disabled
Enabled
Disabled
Configurable Inputs
Coolant Level Sensor
A coolant level sensor is an optional switch input.
Programming the “Coolant Level Sensor” parameter
to “Enabled” notifies the ECM that a coolant level
sensor input is present on pin J1:38. If this parameter
is programmed to “Enabled” and the coolant level
falls below the measured level, a “E2143-3” event
code will be displayed.
Table 28
Value Default
Installed
Not Installed
Not Installed