permaPROC-18-
6.10 Impulse Mode via the Connected Control System
DischargeoflubricatorPROCcanalsobetriggeredviatheattachedcontrolsystem.
Inthiscase,thelubricatordischarges0.5cm
3
lubricanttothelubricationpointeverytimeitisswitchedon.
Forthis,youhavetoswitchonthesupplyvoltageviayourcontrolsystemforatleast14minutesandthenyou
havetoswitchitoffforatleast20seconds.
Theminimumoperatingtimeof14minutesisduetothepossibilitytoconnectthepermaPROCtothedistributor
permaMP-6.Thisdistributorisabletosupplylubricanttouptosixlubricationpoints.
Thismeansthatthedistributorneedsaminimumoperatingtimeof14minutestobeabletosupply1.0cm
3
lubricanttoeveryopendistributoroutlet.
Ifoperatedasasingle-pointlubricationsystem,theminimumoperatingtimeisreducedto1minuteandthe
dischargeamountperimpulse=0.5cm
3
.
ForanactivationofthepermaPROClubricatorviayourcontrolsystem,youneedtosetthelubricator
toimpulsemodeviathecongurationmenu(refertochapter6.8).
Forthis,youhavetoselectthesetting“ “Daysinthesettingmode“Days”(refertogure17).
Outlets
1
3
2
4
5
6
Days
Weeks
Months
%Vol.
LC2500LC2500
Confi g.
TimeTime PIN
Config.
Time
Days
gure17
7. Replacement of the PRO LC unit
The Following Must Always Be Taken into Account
IfthereplacementofanemptyPROLCunitbecomesnecessary,itwillbeindicatedbyasimultaneous
blinkingoftheredandthegreenLED.Additionally,thedisplayindicatesthatthePROLCunitisempty
(refertogure18).
IfthePROLCunitisempty,theconnectedcontrolsystemofyourequipmentreceivesa“Low”signalanda
malfunctionisindicated.
%Vol.
LC 500
gure18
If you replace the PRO LC unit by an PRO LC unit of a different size, a corresponding protection cover
(refer to ”Accessories and Spare Parts”) must be used.
Since the drive unit and the control board must be protected against moisture, an exchange may only
be carried out in dry conditions!
AftertheinstallationofthenewPROLCunit,thecontrolsystemcontinuestooperateusingthepreviouslyvalid
settingofthedischargeperiod.