EasyManua.ls Logo

Perma PRO 500 - Trouble Shooting for MP-6 Distributor; Error Messages and Guides

Perma PRO 500
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
permaPROMP-6Distributor-16-
Indication
of the
display
Error Possible cause Remedial measures
E0
Lubricationsystemhasbeen
switchedoff
Excessmotorcurrentoftheperma
MP-6
ReplacepermaMP-6distributor
F I tof6
Erroratthedisplayed
lubricationpoint
Excessmotorcurrentofthe
lubricatormotorcausedbya
blockingofthedisplayedoutlet
Cleartheblockageand
acknowledgethefaultby
pushingandholdingdownthe
ON/OFF/SELECTorSELECT
button
E2
Lubricationsystemhasbeen
switchedoff
Outletsofdistributornotcorrectly
recognized
Replacedistributor
E3
Lubricationsystemhasbeen
switchedoff
Timeoutwhileactivatingdistributor
Connectioncabledamaged
Replacedistributor
Replaceconnectioncable
e4
Lubricationsystemhasbeen
switchedoff
Drivemechanismofthelubricator
isdefective
Replacethedriveunitofthe
lubricator
E5
Outletcongurationmissing Outletswerenotactivated
Activatedesiredoutlets
(Turnoffpowersupplyon
PROCbeforeyouacknowledge
errormessages)
LC
Lubricationsystemdoesnotdetect
thePROLCunit
NoPROLCunitinstalled
InstallanPROLCunit
(ObservetheOperating
Instructionsofthelubricator)
L
(Onlywith
PRO)
Nopowersuppliedtothe
lubricationsystem
Nopowersuppliedtothelubricator
Establishapowersupply
(ObservetheOperating
Instructionsofthelubricator)
chart3
6. Trouble Shooting
6.1 Error Messages of the Distributor on the Display of the Lubricator
Possibleerrorsofthedistributorandthecompletelubricationsystemaredetectedbytheelectroniccontrolunit
andareindicatedonthedisplayofthelubricator.Forexample,iftheerrormessage isshownonthedisplay,
therequiredpressureatthesecondconnectedlubricationpointexceeds25bar(360psi).
Thismeansthatthislubricationpointisnolongersuppliedwithlubricant.Thedistributorstillprovideslubricant
toallotheractivatedlubricationpoints.Correctthemalfunctionofthesecondlubricationpoint(e.g.greaseline
bentorblocked)andacknowledgeitbypushingtheON/OFF/SELECTbuttononthelubricatorPROorthe
SELECTbuttononlubricatorPROC.
Error messages are acknowledged and reset by pushing the ON/OFF/SELECT or SELECT button.
6.2 Trouble Shooting Guide
Iftherearemalfunctionsduringtheoperationofthedistributororthelubricationsystem,pleasecheckforpos-
siblecausesusingthefollowingchart(refertochart3).Ifyouhavetodealwithamalfunctionthatisnotlisted
inthechartbelow,pleasecontactyourlocalsupplierfortechnicalsupport.
Every time that an error message is shown on the display of the lubricator, the red LED at the lubricator
is also blinking.

Table of Contents

Other manuals for Perma PRO 500

Related product manuals