2 Operating PAL-AT
22
SECURITY CODE “A” ENTERED, LEVEL “B”
LEAK DETECTED IN CABLE “A” AT “B” FEET
NEW CABLE “A” REFERENCE, STORED AS MAP“B”
CABLE “A” MONITORING ON, MAP “B” IN/“YEAR”
CABLE “A” DRYING AT “B” FEET
CABLE “A” SETUP, WITH LENGTH OF “B” FEET
CABLE “A” MONITORING OFF IN /“YEAR”
SHORT DETECTED IN CABLE “A” AT “B” FEET
BREAK DETECTED IN CABLE “A” AT “B” FEET
This entry is stored when a sensor string is setup, "A" is the cable number and "B" is the length of the
sensor string.
LCD2.6-04:
This entry is stored when a new reference or master map is created. "A" is the cable number and "B" is
the map number.
LCD2.6-05:
This entry is stored when a cable is manually put on-line for automatic monitor in the Verify Cable function.
LCD2.6-06:
This entry is stored when a cable is taken off-line.
LCD2.6-07:
This entry is stored when a security code is entered into the unit. "A" is the number of the security code
(1-25) and "B" is the security level for the code (1-255). The master password is level 255.
LCD2.6-09:
This entry is stored when a leak is detected. "A" is the cable number and "B" is the distance where the
leak is first detected.
LCD2.6-10:
This entry is stored when a cable dries.
LCD2.6-11:
This entry is stored when a short is detected.
LCD2.6-12:
This entry is stored when a break is detected.
LCD2.6-13:
This entry is stored when a cable fault is detected in the first 50 ft [15 m] of the cable.