PAL-AT Operating Manual
23
FAULT IN FIRST 50 FEET OF CABLE “A”
NO END FOUND IN CABLE "A" IN "B" FEET
PROBE # “B” RESET IN CABLE “A”
CABLE “A” AUTOSELECT, NOW USING MAP “B”
PROBE # “B” ACTIVATED IN CABLE “A”
ALL NEW EVENTS ACKNOWLEDGED
CABLE “A” AUTOREFERENCE, STORED AS MAP “B”
AUTOMATIC MONITORING ENABLED IN / “YEAR”
AUTOMATIC MONITORING DISABLED IN / “YEAR”
LCD2.6-14:
This entry is stored when the cable is disconnected from PAL-AT or additional cable is improperly added
to the sensor string. "B" is at least 200 ft [60 m] longer than the sensing string setup length.
LCD2.6-15:
This entry is stored when a probe is activated. "B" is the number of the probe.
LCD2.6-16:
This entry is stored when a probe resets to its initial condition, either normally open or normally closed.
LCD2.6-17:
This entry is stored when the alarm queue is cleared.
LCD2.6-18:
This entry is stored when a previous map, "B”, is selected by PAL-AT due to drying cable or a probe reset.
LCD2.6-19:
This entry is stored when a new map "B" is taken by PAL-AT due to drying cable or a probe reset.
LCD2.6-20:
This entry is stored when automatic monitoring is enabled using the "master" password.
LCD2.6-21:
This entry is stored when automatic monitoring is disabled using the "master" password.
LCD2.6-22: