Process, parameter, and diagnostic data
109745_en_01 PHOENIX CONTACT 47 / 66
7.2.1.5 Resetting the application parameters to factory default settings
(index 000F
hex
)
This index allows the application parameters to be reset to factory default settings and is not
part of the startup parameterization. For example, the WRREC block is used to write to this
index. Only application parameters are reset with this index. The communication parame-
ters, such as the station name, I&M data, and IP addresses are retained.
Table 7-13 Resetting the application parameters to factory default settings
Byte
offset
Data
type
Data Access Default setting
0 Byte 10 = reset power module w -
20 = reset power module and all circuit breaker modules