75
5277A
092B An MPM accessor used a communication reference which had not been assigned to this accessor.
092E Not enough free memory space available on the controller board to initialize the Standard Signal Interface (SSGI).
0930 The controller board cannot process the Set_Value_Request (0750
hex
) service due to wrong parameters used when
calling.
0931 The controller board could not process the service called last. A non-defined value was used for the Variable_ID pa-
rameter.
0932 The specified MPM device could not enable the exclusive rights.
0933 The request of the exlusive rights was rejected as a different MPM
accessor still has these rights.
Use the Change_Exclusive_Rights_Request
(014F
hex
) service to enable the exclusive rights
only when no other MPM accessor already has
these rights.
0934 The request of exclusive rights was rejected.
0935 The permissible value range was exceeded when specifiying a
communication reference (CR).
Assign only CRs within the range of: 2≤CR≤63. .
0938 A value which is reserved for the firmware was used for the Variable_ID parameter.
0939 A value which is not enabled was used for the Variable_ID parameter.
Display Description Remedy