80
5277A
0A17 An unknown ID code was assigned. Check the parameters of the configuration
frame.
0A18 An invalid bit was activated in the Used_Attributes parameter. Check the Used_Attributes parameter. The Nos.
0, 1, 3 and 4 are permitted.
0A19 When accessing the configuration frame, the end of the frame was
exceeded.
Check the last access to the configuration
frame.
0A1A The specified Frame_Reference does not exist or cannot be as-
signed.
Check the Frame_Reference parameter.
0A1B The specified configuration frame could not be deleted, as it is cur-
rently activated.
Deactivate the configuration frame with the
Deactivate_Configuration_Request (0712
hex
)
service before deleting.
0A1C The permissible number of specified or connected devices was exceeded.
0A1D The specified configuration frame could not be overwritten. A new
Frame_Reference must be created.
Compare the existing configuration frame with
the new data.
0A1E The next extension could not be assigned to the configuration
frame.
Adapt the size of the new extension to the space
provided.
0A1F The specified configuration frame could not be deactivated, as it is already inactive.
0A20 The physical first INTERBUS device in the data ring was not switched off, as the device cannot be switched off.
Display Description Remedy