82
5277A
0A2E The permissible number of internal indirect entries into address
lists was exceeded.
Reduce the number of devices occupying only
one byte or one nibble of address space.
0A2F The controller board could not process the Initiate_Load_Con-
figuration_Request (0306
hex
) service, as a "0" was entered for the
device number.
Enter the correct number of devices.
0A30 Incorrect entry in the process data description list (PDDL). Check the process data description list.
0A31 The controller board could not process the Put_PDD_List_Request (0321
hex
) service. The device number used does
not exist.
0A32 The controller board could not process the Put_Process_Data_
Description_List_Request (0321
hex
) service, as an invalid value
was entered for the PDD_Index parameter.
Assign values in the range from 0000
hex
to
7FFF
hex
(with the exception of 6010
hex
and
6011
hex
) for this parameter.
0A33 Definition of process output data for a device, which has only input
data or vice versa.
Define the data direction of the process data
description with the Data_Direction parameter:
0C
hex
for IN-PDD, 0D
hex
for OUT-PDD.
0A34 The internal address area of a device was exceeded when describing a process data item.
0A35 A data type and data length were specified that do not match when describing a process data item.
0A36 Error when defining a process data item. A bit string process data
item exceeds the byte boundary.
Do not exceed the byte boundaries of the bit
string process data item.