0A40 Incorrect entry in the process data reference list.
0A41 Incorrect entry in the process data reference list. No OUT-PD was specified as target.
0A42 Incorrect entry in the process data reference list. No IN-PD was specified as source.
0A43 Incorrect entry in the process data reference list. The specified INTERBUS device number does not exist.
0A44 Incorrect entry in the process data reference list. A data consistency was entered for a process data item which does
not match its length.
0A45 Incorrect entry in the process data reference list. A value which does not exist was entered for the PDD_Index
parameter.
0A46 Addressing error. A wrong value was entered for the Compact_
Load_PDRL_Request (0328
hex
) service or Load_PDRL_Request
(0325
hex
) service for the Address_Direction parameter.
Enter 1000
hex
for an input address list, or
2000
hex
for an output address list.
0A47 Incorrect entry in the process data reference list. An incorrect or unknown value was specified for the PDRL_Index
parameter.
0A48 Incorrect definition of a direct link in the PDRL. Check the definitions of direct links.
0A49 The controller board could not start up the bus configuration. A
wrong device number was entered with the Entry_Count parame-
ter for the Compact_Load_PDRL_Request (0328
hex
) service.
Compare the assignment of process data with
the Compact_Read_PDRL_Request (0329
hex
)
service.
Display Description Remedy