84
5277A
0A4A The controller board could not read out the process data reference
list.
Read out the process data reference list with the
Read_PDRL_Request_0327
hex
service.
0A4B Error when assigning a process data item. The bit string process
data item exceeds the byte boundaries.
Note that a bit string process data item does not
exceed the byte boundaries.
0A4C Error when assigning a process data item. An odd MPM address
was assigned.
Assign only even MPM addresses to process
data with a consistency of 16, 32 and 64 bits.
0A50 Error when assigning a process data item. The output address
was assigned several times.
Assign only one process data item to an output
address.
0A51 The controller board did not accept the Frame_Reference parame-
ter.
The value "0" is not permitted for this parameter.
0A55 The configuration data transmitted to the controller board with the
Compare_Configuration_Request (0317
hex
) service does not
match the configuration frame specified by the Frame_Reference
parameter. The device number (segment/position) specified by the
Add_Error_Info parameter has been entered differently.
Check the lists of the transmitted configuration
data and the specified configuration frame.
Display Description Remedy