85
5277A
0A56 The configuration data transmitted to the controller board with the
Compare_Configuration_Request (0317
hex
) service does not
match the configuration frame specified by the Frame_Reference
parameter. The device code (length/ID code) specified by the
Add_Error_Info parameter has been entered differently.
Check the lists of the transmitted configuration
data and the specified configuration frame.
0A57 The configuration data transmitted to the controller board with the
Compare_Configuration_Request (0317
hex
) service does not
match the configuration frame specified by the Frame_Reference
parameter. The device level specified by the Add_Error_Info
parameter has been entered differently.
Check the lists of the transmitted configuration
data and the specified configuration frame.
0A58 The configuration data transmitted to the controller board with the
Compare_Configuration_Request (0317
hex
) service does not
match the configuration frame specified by the Frame_Reference
parameter. The group number specified by the Add_Error_Info
parameter has been entered differently.
Check the lists of the transmitted configuration
data and the specified configuration frame.
0A60 The controller board could not a assign a configuration frame. First create the configuration frame.
0A63 The diagnostic status register and the diagnostic parameter regis-
ter are placed in the output address area.
Place these registers always in the input
address area.
Display Description Remedy