5277A
0A64 Address conflict between a diagnostic register and a process input
data item.
Place the diagnostic status register and the
diagnostic parameter register in address area
which are not assigned by process input data by
using the Set_Value_Request (0710
hex
) service.
0A65 An odd MPM address was assigned to a 16-, 32- or 64-bit register
(this is only allowed for 8-bit registers).
Assign only even addresses to 16-, 32- or 64-bit
registers.
0A70 The controller board could not process the Get_Diag_Info_Request (032B
hex
) service. The reserved attribute could
not be enabled with the Diag_Info_Attr attribute.
0AFB The controller board did not accept the specified data consistency. Check the data assignments of the data consis-
tencies.
0AFC Hardware error on the controller board. Please contact Phoenix Contact.
0AFD The contents of the address decoder EEPROM have changed. Carry out a power-up/reset of the PLC.
0B00 to
0B03
Firmware error on the controller board. Please contact Phoenix Contact.
Display Description Remedy