Chapter 5 Function parameter
30
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page
60.
F2.05
AO1 output lower
limit
0.0% to F2.07
0.0%
59
61.
F2.06
Lower limit
corresponds to AO1
output
0.00V to 10.00V
0.00V
59
62.
F2.07
AO1 output upper
limit
F2.05 to 100.0%
100.0%
59
63.
F2.08
Upper limit
corresponds to AO1
output
0.00V to 10.00V
10.00V
59
64.
F2.09 to
F2.10
Reserved
65.
F2.14
D0 terminal active
status
selection
0x00 to 0x1F
00
59
5-1-5.F3 Group - Start and stop control
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page
66.
F3.00
Start running
mode
0: Directly startup
1: Speed tracking
restart
2: First DC braking and
then start
0
60
67.
F3.01
Startup start
frequency
0.00 to 10.00Hz
0.50Hz
60
68.
F3.02
Hold time for
start frequency
0.0 to 50.0s
0.0 s
60
69.
F3.03
Braking current
before start
0.0 to 150.0%
0.0%
60
70.
F3.04
Braking time
before start
0.0 to 50.0s
0.0 s
60
71.
F3.05
Stop mode
selection
0: Deceleration stop
1: Free stop
0
60
72.
F3.06
Start frequency
of stop braking
0.00 to F0.08
(maximum output
frequency)
0.00Hz
61