EasyManuals Logo

Powtran pi130 series User Manual

Powtran pi130 series
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
Chapter 5 Function parameter
41
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page
source selection
AI1 feedback
1: Analog channel
AI2 feedback
2: Panel
potentiometer
feedback
3: AI1-AI2 feedback
4: Remote
communications
feedback
5: AI1+AI2 feedback
6: MAX (AI1,
AI2)
7: MIN (AI1,
AI2)
168.
E2.03
PID output
selection
0: PID output is
positive
1: PID output is
negative
0
81
169.
E2.04
Proportional gain
(KP)
0.00 to 100.00
1.00
81
170.
E2.05
Integration time
(Ti)
0.01 to 10.00s
0.10s
81
171.
E2.06
Differential time
(Td)
0.00 to 10.00s
0.00 s
81
172.
E2.07
Sampling period
(T)
0.01 to 100.00s
0.10s
82
173.
E2.08
PID control
deviation limit
0.0 to 100.0%
0.0%
82
174.
E2.09
Feedback
disconnection
detection value
0.0 to 100.0%
0.0%
83
175.
E2.10
Feedback
disconnection
detection time
0.0 to 3600.0s
1.0 s
83
5-1-17.E3 Group - Virtual DI, Virtual DO
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page

Table of Contents