Chapter 5 Function parameter
36
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page
117.
F8.04
Motor overload
protection current
20.0% to 120.0%
(rated motor
current)
100.0%
72
118.
F8.05
Overvoltage stall
protection
0: Disable
1: Enable
0
72
119.
F8.06
Overvoltage stall
protection voltage
110 to 150% (220V
series)
115%
72
120.
F8.07
Number of
automatic fault
reset
0 to 3
0
72
121.
F8.08
Automatic fault
reset interval
setting
0.1 to 100.0s
1.0 s
72
122.
F8.09
Descending
frequency point of
momentary power
failure
70.0 to 110.0%
(standard bus
voltage)
80.0%
73
123.
F8.10
Frequency fall
rate at momentary
power failure
0.00Hz/s to F0.08
(maximum output
frequency)
0.00Hz/s
73
5-1-11.F9 Group - Communication parameter
No.
Code
Parameter name
Setting range
Factory
default
Change
Reference
page
124.
F9.00
Communication
baud rate setting
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
3
73
125.
F9.01
Data bits parity
settings
0: no parity (N, 8, 1) for
RTU
1: even parity (E, 8, 1)
for RTU
2: odd parity (O, 8, 1) for
RTU
3: no parity (N, 8, 2) for
RTU
4: even parity (E, 8, 2)
for RTU
1
73