When multi-speed is selected as frequency source, the 100.0% of function code E1.00
to E1.015 corresponds to maximum output frequency F0.08.
Multi-stage command is used for the function of multi-speed, also for PID setting
source to meet the need to switch between different setting values.
When PID is selected as the frequency source, that is to choose 6 for F0.02, the group
function will be enabled. This parameter is used to select the process PID target value
setting channel.
The amount of process PID setting target is a relative value, the set 100% corresponds
to the 100% of feedback signal of the controlled system.
The system always operate in relative value (0 to 100.0%) .
Note: The multi-speed setting can be achieved by setting the parameters of E1 group.