Chapter 5 Function parameter
69
Code
Parameter name
Setting range
Factory
default
Change
In the transition process of setting forward and reverse running of inverter, output
transition time at zero frequency.
F7.09
Power terminals running
protection selection
Terminal running
command is invalid
when it powers on
0
0
Terminal running
command is valid when
it powers on
1
If the running command channel is set to terminal control, the system automatically
detects the status of the running terminals when the inverter powers on.
Terminal running command is invalid when it powers on. Even if the command
terminal is detected as valid when it powers on, the inverter will not run, the system
enters the protection stauts until undoing the running command terminal and then
enabling the terminal again.
Terminal running command is valid when it powers on. Namely that the running
command terminal is detected as valid when the inverter powers on, once the
initialization is complete, the system will automatically start the inverter.
Note that the user must be careful to select the function, it may cause serious
consequences.
F7.10
FDT level detection value
0.00 to F0.08 (maximum
output frequency)
50.00Hz
F7.11
FDT hysteresis detection
value
0.0 to 100.0% (FDT level)
5.0%
Output
frequency(f)
Forward
Reverse
Deadband time
Time(t)
Schematic diagram of Forward/reverse rotation deadband