EasyManuals Logo

ProMinent DULCO flex Control Supplementary Operating Instructions

ProMinent DULCO flex Control
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Tab. 4: 0x5100 – 0x5500
Index W Name Type Description
Max
Objects Attr
5100h 1 Switch-on
counter
U32 Switch-on counter SDO RO
5101h 1 Error flags U32 Bit 0 - Error, configuration data
(system)
Bit 1 - Error, current input too low
Bit 2 - Error, current input too high
Bit 3 - Error, level
Bit 4 - Error, hose rupture
Bit 6 - Error, directional change
Bit 7 - Error, temperature too high
Bit 8 - Error, initialisation (system)
Bit 9 - Reserved
Bit 10 - Error, invalid metering
parameter
Bit 11 - Reserved
Bit 12 - Reserved
Bit 13 - Error, undervoltage
Bit 14 - Reserved
Bit 15 - Error, hose change
aborted
Bit 16 - Error, memory overflow
Bit 17 - Error, input current less
than limit value
Bit 18 - Error, input current greater
than limit value
Bit 19 - Reserved
Bit 20 - Reserved
Bit 21 - Reserved
Bit 22 - Error, internal CAN bus
Bit 23 - Error, component version
compatibility
Bit 24 - Error, power unit configura‐
tion data
Bit 25 - Error, power unit initialisa‐
tion
Bit 26 - Speed control
Bit 27 - Error, fan
Bit 28 - Error, motor connection
Bit 29 - Error, motor status
Bit 30 - Error, motor blockage
Bit 31 - Error, power unit position
sensor
SDO RO
Supplementary operating instructions for CANopen
13

Table of Contents

Other manuals for ProMinent DULCO flex Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCO flex Control and is the answer not in the manual?

ProMinent DULCO flex Control Specifications

General IconGeneral
BrandProMinent
ModelDULCO flex Control
CategoryWater Pump
LanguageEnglish

Related product manuals