Module
/ slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
bit Name Function
19 Hose
rupture
sensor
Hose rupture
sensor is
installed
20 Con‐
centra‐
tion
Concentration
calculation is acti‐
vated
21 - -
22 - -
23 - -
24 - -
25 - -
26 - -
27 - -
28 - -
29 - -
30 - -
31 - -
2 1 Start /
Stop
Control 80.81 u8 W Corresponds to the
[Start / Stop]
key;
if Start / Stop = 0, then the pump is
stopped
2 Reset u8 If the reset value is changed from 1
to 0, the internal pump memory is
cleared,
e.g. with batch metering,
and pending errors are deleted, as
far as possible.
The following are reset to “0”:
n deletable rotation counter
n deletable metering quantity
counter
n remaining metering quantity
counter
n volume to be metered in “Batch
mode”
n Clear error requiring acknowl‐
edgement
* R = read, W = write
Tab. 34: Mode, Flow rate, Max. flow rate, Batch, Contact, Concentration, Metering monitor
Module
/ slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
3 1 Mode Mode C0,80,8
0
u8 R, W Value Name Description
0.16 Halt Pump is ready
but not metering.