EasyManuals Logo

ProMinent DULCO flex Control Supplementary Operating Instructions

ProMinent DULCO flex Control
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
Module
/ slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
1 Manual Pump is metering
continuously with
the set volume
2 Batch When triggered,
the pump is
metering the
volume set in the
batch pre-selec‐
tion
3 Contact Pump is metering
volumes in the
specified time
R, W 4 Ana‐
logue
Pump is metering
in accordance
with the analogue
signal and ana‐
logue mode set
on the pump.
17 Manual
(con‐
centr.)
Manual in con‐
centration mode
18 Batch
(con‐
centr.)
Batch in concen‐
tration mode
19 Contact
(con‐
centr.)
Contact in con‐
centration mode
20 Ana‐
logue
(con‐
centr.)
Analogue in con‐
centration mode
Setting Bit 4
(+16) activates
concentration
mode (e.g. set
“Analogue
normal” with “4”;
set “Analogue
concentration”
mode with “20”)
Setting Bit 7
(+128) sets the
direction of rota‐
tion
Bit 7 = 1 ->
Counter-clock‐
wise rotation
Bit 7 = 0 ->
Clockwise rota‐
tion
4 1 Nominal
flow
rate
Flow
rate
C0,83,8
3
f32 W Dosing rate setpoint in litres / hour
2 Actual
flow
rate
f32 R Dosing rate actual value
Supplementary operating instructions for PROFIBUS
®
56

Table of Contents

Other manuals for ProMinent DULCO flex Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCO flex Control and is the answer not in the manual?

ProMinent DULCO flex Control Specifications

General IconGeneral
BrandProMinent
ModelDULCO flex Control
CategoryWater Pump
LanguageEnglish

Related product manuals