Diagnostics and Troubleshooting MVI56E-MCM ControlLogix Platform
User Manual Modbus Communication Module
Page 118 of 209 ProSoft Technology, Inc.
Bit
Description
Value
5
Baud rate parameter is not valid.
0x0020
6
Parity parameter is not valid.
0x0040
7
Data bits parameter is not valid.
0x0080
8
Stop bits parameter is not valid.
0x0100
9
Slave ID is not valid.
0x0200
10
Input bit or word, output word and/or holding register
offset(s) are not valid.
0x0400
11
Command count parameter is not valid.
0x0800
12
Spare
0x1000
13
Spare
0x2000
14
Spare
0x4000
15
Spare
0x8000
Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.
Note: If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this indicates a
serious problem with the module. Call ProSoft Technology Support to arrange for repairs.

Table of Contents

Other manuals for ProSoft Technology MVI56E-MCMXT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft Technology MVI56E-MCMXT and is the answer not in the manual?

ProSoft Technology MVI56E-MCMXT Specifications

General IconGeneral
BrandProSoft Technology
ModelMVI56E-MCMXT
CategoryControl Unit
LanguageEnglish

Related product manuals