TempTracker mod+ Hybrid Installation and Operation Manual 15
HTC# 059105-00D

(A Terminals 13, 14), (B Terminals 16, 17),...
The TempTracker mod+ Hybrid can operate up to four 4-20 mA modulating motors.
The Extension can operate up to six 4-20 mA modulating motors.
The TempTracker mod+ Hybrid and the Extension sources excitation voltage for the 4-20mA signal.
Wire the (-) from the boiler modulating motor to the (GND) terminal on the TempTracker mod+ Hybrid. That is
for boiler A, the modulating (GND) terminal will be 13.
Wire the (+) from the boiler modulating motor to the (mA+) terminal on the TempTracker mod+ Hybrid. That is
for boiler A, the modulating (mA+) terminal will be 14.
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
HYBRID
Boiler 4-20mA
Modulation Output
4-20mA
Burner
Motor
-
+
OD=55
o
F SYS=142
o
F
<A> B
80% 50%
STAGEMENU


(A Terminals 13, 15), (B Terminals 16, 18),...
The TempTracker mod+ Hybrid can operate up to four 0-10V modulating motors.
The Extension can operate up to six 0-10V modulating motors.
Wire the (GND) from the boiler modulating motor to the (GND) terminal on the TempTracker mod+ Hybrid. That
is for boiler D, the modulating (GND) terminal will be 22.
Wire the (VLT+) from the boiler modulating motor to the (VLT+)terminal on the TempTracker mod+ Hybrid.
That is for boiler D, the modulating (VLT+) terminal will be 23.
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
HYBRID
Boiler Voltage
Modulation Output
Voltage
Burner
Motor
GND
V+