EasyManuals Logo

Raypak TempTracker mod+ Hybrid User Manual

Raypak TempTracker mod+ Hybrid
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
TempTracker mod+ Hybrid Installation and Operation Manual 33
HTC# 059105-00D

Button: MENU/<System Settings>
Settings 1 and Settings 2 menus provide access to adjusting and ne-tuning the system for
enhanced comfort and better fuel savings. The TempTracker mod+ Hybrid behaves differently
based on the selected modes. See "Startup Settings" on page 20.
-----SETTINGS1----
Setback 0
o
F
PurgeDelay 1.0min
SystemRun-On 0min
LeadRotation Time
<MoreSettings>
BACKSELECT
-----SETTINGS2----
StandbyTime 10min
LastStgHold 0
o
F
<LeadStages>
<StagingSettings>
<MdlatingSettings>
<Day/NightSchdule>
BACKSELECT
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
HYBRID

To be able to change the TempTracker mod+ Hybrid settings the Program/Run
Switch must be set to Program. The switch is located under the Enclosure Wiring
Cover for security. The Enclosure Wiring Cover can be secured using a lock.

Adjustablefrom0F°/0C°to75F°/42C° Default:10F°/6C°
Button: MENU/<System Settings>/Setback
The Setback feature can be used to provide the TempTracker mod+ Hybrid with a lower
temperature Set Point when less load is required.
The lower Set Point will appear on the main display indicating this condition.
For example, if the calculated temperature is 180°F and the Setback is 20°F, then when in
Setback or Night Schedule, the TempTracker mod+ Hybrid will hold a Set Point of 160°F =
180°F- 20°F. See "Day/Night Schedules" on page 37.
A typical use for the Setback is to provide less system temperature to a building during
the Night Schedule or on the weekends when people are asleep or when the building is not
occupied, but heat is still needed.
The amount of Setback selected is subtracted from the Set Point when a Setback Input
Signal is received or the Night Time schedule setting started.
If Setback is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/Setback
Mode" on page 26.), the Setback will not be activated unless a Short dry-contact signal is
received on terminals (31 and 32).
If Shutdown or Tstat is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/
Setback Mode" on page 26.), the Setback will be activated only during the Night Schedule.
-------SETBACK-------
10
o
F
[ ]
BACKSAVE

When using Soft-Off and Last
Stage Hold, the last boiler
stage will not turn off until both
parameters have elapsed. In
this case, Soft-Off will start after
the Last Stage Hold.

Adjustablefrom0.0minto10.0min Default:1.0min
Button: MENU/<System Settings>/Purge Delay
Many boilers go through a purge cycle before they are brought on line. When the
TempTracker mod+ Hybrid activates a boiler, it does not start to calculate its output until
the Purge Delay is over. This allows the boiler to fully come online and begin producing.
The Purge Delay helps prevent short cycling of any newly activated burner. Once the
burner is activated, it MUST run through the entire Purge Delay period.
The minimum Purge Delay setting MUST be set to the time required by the boiler
manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5 minute will equal 90 seconds.)
The Message Display Line will display PurgeDelay and the remaining time.
---PURGEDELAY---
1.0min
[ ]
BACKSAVE

Set Purge Delay as per boiler
manufacturer recommendation.

Adjustablefrom0minto360min Default:10min
Button: MENU/<System Settings>/System run-On
A common use for the System Run-On is to control a system pump in a heating system.
The extra time helps transfer the boiler residual heat to the heating system.
The System relay will energize whenever the outdoor temperature is below the Outdoor
Cutoff and the Shutdown is Open or the Tstat is closed. When the Outdoor temperature
rises 2°F above the Outdoor Cutoff or the control is switched to Summer and after the last
burner relay has de-energized, the System relay will remain energized for the System Run-
On period.
--SYSTEMRUN-ON--
10min
[ ]
BACKSAVE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raypak TempTracker mod+ Hybrid and is the answer not in the manual?

Raypak TempTracker mod+ Hybrid Specifications

TempTracker mod+ Hybrid

Operating Environment IconOperating Environment
operating temperature20°F/-6°C to 130°F/54°C
operating humidity20% to 80% non-condensing
control sensor rangesminus 35°F/-37°C to 250°F/121°C
Power IconPower
voltage input120 VAC 60 Hz
power consumption12 VA Max
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
Weight and Dimensions IconWeight and Dimensions
dimensions11"W x 9" H x 3 ¾" D
weight2.5 pounds

TempTracker mod+ Hybrid

Power IconPower
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
power backupLithium coin battery, 100 days minimum
add-on extension panelsup two Extension Panels using RS485 (RJ45 or RJ11)
Temperature Control IconTemperature Control
ignition point1 to 50%
modulation start point0 to 100%
outdoor cutoff range20°F/-6°C to 100°F
Operating Environment IconOperating Environment
minimum water temperature50°F/10°C to 170°F/77°C
maximum water temperature90°F/32°C to 240°F/116°C
offset adjustmentminus -40°F°/-22°C° to plus 40°F°/22°C°

Extension

Output Specifications IconOutput Specifications
boiler outputs(6) N.O. S.P.S.T.
modulating output types(6) 4-20mA and 0-10V
output relay ratings1 Amp inductive (⅛ HP), 6Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits

Related product manuals