TempTracker mod+ Hybrid Installation and Operation Manual 29
HTC# 059105-00D


To be able to change the
TempTracker mod+ Hybrid settings
the Program/Run Switch must
be set to Program. The switch is
located under the Enclosure Wiring
Cover for security. The Enclosure
Wiring Cover can be secured using
a lock.
--------SETTINGS----
Season Winter
SystemTarget140
o
F
<SystemSettings>
<Maintenance>
<SystemStartup>
BACKSELECT
-----SEASON-----
Winter
Summer
BACKSAVE
-----SETTINGS1----
Setback 10
o
F
PurgeDelay 1.0min
SystemRun-On10min
LeadRotation Time
<MoreSettings>
BACKSELECT
-------SETBACK-------
10
o
F
[ ]
BACKSAVE
---PURGEDELAY---
1.0min
[ ]
BACKSAVE
--SYSTEMRUN-ON--
10min
[ ]
BACKSAVE
--LEADROTATION--
Manual
Time
Last-On
BACKSAVE
-----SETTINGS2----
StandbyTime 10min
LastStgHold 5
o
F
<LeadStages>
<StagingSettings>
<MdlatingSettings>
<Day/NightSchdule>
BACKSELECT
--STANDBYTIME--
10min
[ ]
BACKSAVE
LASTSTAGEHOLD
5
o
F
[ 
]
BACKSAVE
---LEADSTAGES---
CondLead A
Non-CondLead C
BACKSAVE
-STAGESETTINGS-
ReactionTime 2min
MinimumRuntime2min
BACKSAVE
MODULATIONSETTINGS
Gain +0
LagDelay 0min
Soft-OffDelay45sec
BACKSAVE
DAY/NIGHTSCHEDULE
SetTime **:**
DaySchedule 6:00a
NightSchedule8:00p
BACKSAVE
OD=55
o
FSYS=143
o
F
<A> B
67% 22%
STAGEMENU
-SYSTEMTARGET--
1.00
o
OD=4.00
o
Sys
1.00
o
OD=3.00
o
Sys
1.00
o
OD=2.00
o
Sys
1.00
o
OD=1.50
o
Sys
1.00
o
OD=1.25
o
Sys
1.00
o
OD=1.00
o
Sys
1.25
o
OD=1.00
o
Sys
1.50
o
OD=1.00
o
Sys
2.00
o
OD=1.00
o
Sys
3.00
o
OD=1.00
o
Sys
4.00
o
OD=1.00
o
Sys
BACKSAVE
-------OFFSET------
+0
o
F
[ 
]
BACKSAVE
-OUTDOORCUTOFF-
65
o
F
[ ]
BACKSAVE
MINIMUMWATERTEMP
70
o
F
[ 
]
BACKSAVE
MAXIMUMWATERTEMP
200
o
F
[ ]
BACKSAVE

-----SETPOINT-----
0
o
F
[ 
]
BACKSAVE
-OUTDOORCUTOFF-
65
o
F
[ ]
BACKSAVE
