TempTracker mod+ Hybrid Installation and Operation Manual 9
HTC# 059105-00D

Two Setback modes are available for the TempTracker mod+ Hybrid:
The Day/Night Scheduling provides an adjustable time-based schedule for the Setback (only available when Shutdown or Tstat is
selected as the Setback/Shutdown Startup option). See "Shutdown/Tstat/Setback Mode" on page 26.
The Setback mode uses an external signal to switch the operation of the TempTracker mod+ Hybrid in and out of setback mode (only
available when Setback is selected as the Setback/Shutdown Startup option).

By connecting the control to the optional 4-20mA EMS Interface, the control shall be capable of accepting a remote set point.

An optional BACnet Interface Module (#651735) can be used to connect the control to a BACnet MSTP network for remote access.

If you need the TempTracker mod+ Hybrid to do additional tasks that either are not listed or do not know how to congure them,
contact your local Raypak representative.
Setting an Initial Program will ease the conguration of the TempTracker mod+ Hybrid and will give the opportunity to utilize many of
the energy saving features while giving comfortable heat when needed.
The program should consist of the following:
Selecting the features that your system can utilize.
Installation: Install the Control, switches and sensors. See"Installation" on page 10
Setting the System Startup. See "Startup Settings" on page 20.
Setting the System Operating Settings. See "Operating Settings" on page 31
Setting the Stages. See "Modulating Boiler Operating Settings" on page 35. Also, see "Staging Boiler Operating Settings" on page 36
Adjusting Reset Ratio and Water Offset (In Reset Mode Only). See "Reset Ratio" on page 31

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raypak TempTracker mod+ Hybrid and is the answer not in the manual?

Raypak TempTracker mod+ Hybrid Specifications

TempTracker mod+ Hybrid

Operating Environment IconOperating Environment
operating temperature20°F/-6°C to 130°F/54°C
operating humidity20% to 80% non-condensing
control sensor rangesminus 35°F/-37°C to 250°F/121°C
Power IconPower
voltage input120 VAC 60 Hz
power consumption12 VA Max
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
Weight and Dimensions IconWeight and Dimensions
dimensions11"W x 9" H x 3 ¾" D
weight2.5 pounds

TempTracker mod+ Hybrid

Power IconPower
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
power backupLithium coin battery, 100 days minimum
add-on extension panelsup two Extension Panels using RS485 (RJ45 or RJ11)
Temperature Control IconTemperature Control
ignition point1 to 50%
modulation start point0 to 100%
outdoor cutoff range20°F/-6°C to 100°F
Operating Environment IconOperating Environment
minimum water temperature50°F/10°C to 170°F/77°C
maximum water temperature90°F/32°C to 240°F/116°C
offset adjustmentminus -40°F°/-22°C° to plus 40°F°/22°C°

Extension

Output Specifications IconOutput Specifications
boiler outputs(6) N.O. S.P.S.T.
modulating output types(6) 4-20mA and 0-10V
output relay ratings1 Amp inductive (⅛ HP), 6Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits