EasyManua.ls Logo

Raypak TempTracker mod+ Hybrid - Startup Settings; Startup Sequence; Boiler Type; Sensor Type

Raypak TempTracker mod+ Hybrid
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 Raypak, Inc.
HTC# 059105-00D


To be able to change the TempTracker mod+ Hybrid settings the Program/Run Switch must be
set to Program. The switch is located under the Enclosure Wiring Cover for security.
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
/TSTAT
HYBRID

Button: MENU/<System Startup>
When powered, the TempTracker mod+ Hybrid performs a self diagnostics-test.
On the rst power up, the System Startup screen will appear after the initialization is
complete. If it doesn’t, the TempTracker mod+ Hybrid has already been congured.
The System Startup menu sets the main parameters that relate to the heating application.
These settings must be set by the installer.
--------SETTINGS----
Season Winter
SystemTarget140
o
F
<SystemSettings>
<Maintenance>
<Histories>
<SystemStartup>
BACKSELECT

Modulation,Staging,Hybrid Default:Modulation
Button: MENU/<System Startup>/..../Boiler Type
The same Raypak control can operate modulating boilers, staging boilers, or a combination
of both types.
The Modulation option will operate a variety of modulating boilers.
The Staging option will operate a variety of On/Off or multi-stage boilers.
The Hybrid option will sequence two groups of boilers, condensing and non-condensing.
Each group could be of a different boiler type (Modulation or Staging). See "HYBRID
Startup Settings" on page 21. Each Multi-Stage boiler will use a single output relay. The
staging will take place using the voltage output signal.
If BACnet is to be used, each of the Boiler Type modes will have a different set of BACnet
variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44..
---BOILERTYPE---
Modulation
Staging
Hybrid
BACKSAVE

Reset°F,Reset°C,SetPoint°F,SetPoint°C,4-20mAEMS Default:Reset°F
(Set Point Options Not Available with Hybrid Boiler Type)
Button: MENU/<System Startup>/..../Sensor Type
If Reset °F is selected, all temperatures and settings will be displayed in degrees Fahrenheit
and the control will use Reset Ratios to adjust the system set point.
If Reset °C is selected, all temperatures and settings will be displayed in degrees Celsius and
the control will use Reset Ratios to adjust the system set point.
If Set Point °F is selected, all temperatures and settings will be displayed in degrees
Fahrenheit and the control will have an adjustable system set point.
If Set Point °F is selected, all temperatures and settings will be displayed in degrees Celsius
and the control will have an adjustable system set point.
The 4-20mA EMS option is only available to the Hybrid Boiler Type option. To use
4-20mA EMS with Staging and Modulating Boiler Types, select one of the Set Point options
and the EMS Input Mode menu will follow to offer the 4-20mA EMS option.
The use of the 4-20mA EMS option requires the purchase of the 4-20mA EMS Interface
(#012019). It gives the TempTracker mod+ Hybrid the capability of accepting a remote
4-20mA signal from a BMS or EMS system as the target set point.
If BACnet is to be used, each of the Sensor Type modes will have a different set of BACnet
variables. See "Hybrid - Outdoor Reset - BACnet Variable list" on page 44..
--SENSORTYPE--
Reset
o
F
Reset
o
C
SetPoint
o
F
SetPoint
o
C
BACKSAVE
---SENSORTYPE---
Reset
o
F
Reset
o
C
4-20mAEMS
BACKSAVE

Disable,Enable Default:Disable
(Available after Set Point with Staging or Modulation Boiler Types)
Button: MENU/<System Startup>/..../Boiler Type/Sensor Type / EMS Input Mode
It allows the TempTracker mod+ Hybrid to utilize the 4-20mA EMS Interface (#012019) to
accept a remote 4-20mA signal from a BMS or EMS system as the target set point.
-EMSINPUTMODE-
Disable
Enable
BACKSAVE

Table of Contents

Related product manuals