TempTracker mod+ Hybrid Installation and Operation Manual 49
HTC# 059105-00D

    
TempTracker mod+ Hybrid BACnet
Control
Varies 1.5 2.0 2.0
  
Raypak, Inc. 477 2151 Eastman Ave., Oxnard, CA 93030 - (805)278-5300

TempTracker mod+ Hybrid control for hot water heating applications. (see http://www.raypak.com for more information)

 
TempTracker mod+ Hybrid BACnet Control BACnet Application Specic Controller (B-ASC)

 
DS-RP-B Data Sharing-ReadProperty-B
DS-WP-B Data Sharing-WriteProperty-B
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DCC-B Device Management-DeviceCommunicationControl-B

  
Analog Value No No
Binary Value No No
Multi-State Value No No
Device No No

  
TempTracker mod+ Hybrid BACnet Control BACnet MS/TP
Baud Rates: 9600, 19200, 38400

  
Able to transmit segmented messages No
Able to receive segmented messages No

 
TempTracker mod+ Hybrid BACnet Control No

 
TempTracker mod+ Hybrid BACnet Control ANSI X3.4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raypak TempTracker mod+ Hybrid and is the answer not in the manual?

Raypak TempTracker mod+ Hybrid Specifications

TempTracker mod+ Hybrid

Operating Environment IconOperating Environment
operating temperature20°F/-6°C to 130°F/54°C
operating humidity20% to 80% non-condensing
control sensor rangesminus 35°F/-37°C to 250°F/121°C
Power IconPower
voltage input120 VAC 60 Hz
power consumption12 VA Max
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
Weight and Dimensions IconWeight and Dimensions
dimensions11"W x 9" H x 3 ¾" D
weight2.5 pounds

TempTracker mod+ Hybrid

Power IconPower
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
power backupLithium coin battery, 100 days minimum
add-on extension panelsup two Extension Panels using RS485 (RJ45 or RJ11)
Temperature Control IconTemperature Control
ignition point1 to 50%
modulation start point0 to 100%
outdoor cutoff range20°F/-6°C to 100°F
Operating Environment IconOperating Environment
minimum water temperature50°F/10°C to 170°F/77°C
maximum water temperature90°F/32°C to 240°F/116°C
offset adjustmentminus -40°F°/-22°C° to plus 40°F°/22°C°

Extension

Output Specifications IconOutput Specifications
boiler outputs(6) N.O. S.P.S.T.
modulating output types(6) 4-20mA and 0-10V
output relay ratings1 Amp inductive (⅛ HP), 6Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits