TempTracker mod+ Hybrid Installation and Operation Manual 3
HTC# 059105-00D

In response to new advancement in condensing boiler design and size, many applications utilize multiple condensing boilers in
addition to the non-condensing boilers. That triggered Raypak's patent design of the TempTracker mod+ Hybrid . It is intended to
manage the two groups of boilers to maximize system efciency at the lowest operating cost while maintaining the desired comfort.
When Hybrid is selected as the Boiler Type, the TempTracker mod+ Hybrid will operate each group based on the Target temperature
switching set point. See "Boiler Type" on page 20..
Each of the condensing and non-condensing groups of boilers can be either modulating or staging. Modulating boilers can be of
4-20mA modulating signal or 0-10V modulating signal.
Staging boilers must be of the 0-10V signal.
Depending on the actual System Temperature, the
TempTracker mod+ Hybrid will determine which
group of boilers will be the lead and which group will
be the lag group. The Condensing group of boilers
will be the Lead group when the System temperature
is below the System Target Switching Set Point.
However, when the System temperature rises above the
Switching Set Point, the Non-Condensing boiler group
will be the lead group and the Condensing Group will
be the lag group.
Basically, the TempTracker mod+ Hybrid will allow
the condensing group of boilers to operate as along as
the System sensor is below the Switching Set Point.
See"Switch Set Point" on page 21. During that period,
if additional output boilers are needed, the TempTracker mod+ Hybrid will energize the Non-Condensing boilers to meet the load.
See"Heavy Load Sequence 2nd Group" on page 22. When less output is required the TempTracker mod+ Hybrid will de-energize the
Non-Condensing boilers prior to de-energizing the Condensing boilers.
To eliminate any short-cycling due to rapid changes in the Target Temperature used in the switching, an adjustable Switching Delay
has been incorporated. See"Switch Delay" on page 22.
For Hybrid settings, See "Boiler Type" on page 20. See "HYBRID Startup Settings" on page 21.
To set the Condensing and Non-Condensing boiler types See "HYBRID Modulating Boiler Settings" on page 23. Also, See "HYBRID
Staging Boiler Settings" on page 23.
Above the Switch Set Point
Non-Condensing are the Lead Group
Condensing are the Lag Group
Target Switch
Set Point
= 120°F
Below the Switch Set Point
Condensing are the Lead Group
Non-Condensing are the Lag Group
120°F
140°F
100°F
SWITCH MODE = Target Temperature
CONDCOND
NON-
COND
NON-
COND
NON-
COND
NON-
COND
CONDCOND
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7 8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mAGND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mAGND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
OD=
25
o
F SYS=
145
o
F
<<A>> B
100% 52%
System
Temp
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7 8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mAGND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mAGND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
OD=
25
o
F SYS=
145
o
F
<<A>> B
100% 52%
Above the Switch Set Point
Condensing are the Lead Group
Non-Condensing are the Lag Group
Outdoor Switch
Set Point
= 30°F
Below the Switch Set Point
Non-Condensing are the Lead Group
Condensing are the Lag Group
30°F
50°F
10°F
SWITCH MODE = Outdoor Temperature
CONDCOND
NON-
COND
NON-
COND
NON-
COND
NON-
COND
CONDCOND
Outdoor
Temp
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7 8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mAGND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mAGND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
OD=
25
o
F SYS=
145
o
F
<<A>> B
100% 52%
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7 8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mAGND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mAGND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
OD=
25
o
F SYS=
145
o
F
<<A>> B
100% 52%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raypak TempTracker mod+ Hybrid and is the answer not in the manual?

Raypak TempTracker mod+ Hybrid Specifications

TempTracker mod+ Hybrid

Operating Environment IconOperating Environment
operating temperature20°F/-6°C to 130°F/54°C
operating humidity20% to 80% non-condensing
control sensor rangesminus 35°F/-37°C to 250°F/121°C
Power IconPower
voltage input120 VAC 60 Hz
power consumption12 VA Max
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
Weight and Dimensions IconWeight and Dimensions
dimensions11"W x 9" H x 3 ¾" D
weight2.5 pounds

TempTracker mod+ Hybrid

Power IconPower
output relay ratings1 Amp inductive (⅛ HP), 6 Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits
power backupLithium coin battery, 100 days minimum
add-on extension panelsup two Extension Panels using RS485 (RJ45 or RJ11)
Temperature Control IconTemperature Control
ignition point1 to 50%
modulation start point0 to 100%
outdoor cutoff range20°F/-6°C to 100°F
Operating Environment IconOperating Environment
minimum water temperature50°F/10°C to 170°F/77°C
maximum water temperature90°F/32°C to 240°F/116°C
offset adjustmentminus -40°F°/-22°C° to plus 40°F°/22°C°

Extension

Output Specifications IconOutput Specifications
boiler outputs(6) N.O. S.P.S.T.
modulating output types(6) 4-20mA and 0-10V
output relay ratings1 Amp inductive (⅛ HP), 6Amp resistive at 120 VAC 60 Hz, 15 A total for all circuits