TempTracker mod+ Hybrid Installation and Operation Manual 47
HTC# 059105-00D

  





 
Model Device Object MODEL
Serial Number Device Object SNUMBER
Version Device Object VERSION
Operation Mode 100 MULTISTATE-VALUE OPMODE 1 6 1=Modulation Reset, 2= Staging Reset,3=Hybrid Reset, 4=Modulation Setpoint,
5=Staging Setpoint, 6=Hybrid EMS
Outdoor Temperature 200 ANALOG-VALUE ODTEMP Degree F 32000=OPEN,3201=SHORT
System Temperature 300 ANALOG-VALUE SYSSEN Degree F 32000=OPEN,3201=SHORT
Output Status 400 ANALOG-VALUE OPTSTAT 0 0x1FFFF Each Bit represents one of the possible 16 relays. Bit 0 represents Relay1, Bit 16
represents Relay16. 0 = Relay OFF, 1 = Relay ON
Control Status 500 MULTISTATE-VALUE CSTAT 1 13 1=SHUTDOWN,2=NO TSTAT CALL,3=PROVE FAILURE,4=SHUTDOWN
BY EMS,5=WAITING FOR PROVE,6=SENSOR FAULT,7=LAST STAGE
HOLD,8=DHW CALL,9=SUMMER,10=BOOST MODE,11=SYSTEM
RUNON,12=SETBACK MODE,13=OUTDOOR CUTOFF
Season 600 MULTISTATE-VALUE SEA 1 2 1= Winter, 2= Summer
Setpoint 700 ANALOG-VALUE SETP Degree F 70 250 Integer Values Only (70,71,72…)
Outdoor Cutoff 800 ANALOG-VALUE CO Degree F 19 101 Integer Values Only (19,20,21…)
Setback 900 ANALOG-VALUE SB Degree F 0 75 Integer Values Only (0,1,2…)
Purge Delay 1000 ANALOG-VALUE PDLY Minutes .1 10 .1 thru .9 after Integer Values Only (1,2,3…)
System Runon 1100 ANALOG-VALUE RUNON Minutes 0 360 Integer Values Only (0,1,2…)
Rotation Time 1200 ANALOG-VALUE RTTIME Hours 1 1440 Hours since last rotation Integer Values Only (1,2,3…)
Standby Time 1300 ANALOG-VALUE STBYDLY Minutes 1 60 Integer Values Only (1,2,3…)
Last Stage Hold 1400 ANALOG-VALUE LSTHOLD Degree F 0 30 Integer Values Only (0,1,2…)
Con Lead Stage 1500 MULTISTATE-VALUE CLEAD 1 16 Represent the current lead boiler for the condensing group
Non-Con Lead Stage 1600 MULTISTATE-VALUE NCLEAD 1 16 Represent the current lead boiler for the non-condensing group
Gain 1700 MULTISTATE-VALUE GAIN 1 10
Lag Delay 1800 ANALOG-VALUE LAGDLY Minutes 0 60 Integer Values Only (0,1,2…)
Soft off 1900 ANALOG-VALUE SOFF Seconds 0 60 Integer Values Only (0,1,2…)
Set Time 2000 ANALOG-VALUE PTIME Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Day Schedule 2100 ANALOG-VALUE DSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)
Night Schedule 2200 ANALOG-VALUE NSCHED Minutes 1 1440 Time since midnight Integer Values Only (1,2,3…)