Problem 2 The tube motor does not stop or get at the set end posion.
Observaon 2 The end posions are erased or set again.
Cause 1 Moist condions caused a short circuit.
Soluon 1 Repair the electrical connecons. Set the end posions again.
Cause 2 Inducon caused an interference with the electronics.
Soluon 2 Prevent problems with inducon. Refer to §5.2.
• Are the cables not too long?
• Do external sources not cause problems?
• Is there a separaon of cables for each tube-motor connecon?
Cause 3 The decreased braking funcon of the tube motor caused the end of the lifespan.
Soluon 3 Replace the tube motor. Set the end posions.
Do a check of the condions and starng points in §5.2.
• Is there no undervoltage less than 190 V?
• Are problems with inducon prevented?
• Is the load less than the maximum switch-contact load for the switch installaon
(relay controls, switches and such)?
Do a check of the condions and starng points in § 6.1.
Is the duty cycle correct?
Problem 3 The second end posion is not set aer the programming buon is pushed.
Observaon 3 The tube motor does not give a “click”.
Cause 1 End posions that are set again and again caused an interference with the
electronics.
Soluon 1.1 Release the programming buon (refer to step 5 of the procedure) and push it
again for a minimum of 3 seconds. Usually this will set the second end posion
correctly.
Soluon 1.2 De-energize the tube motor. Wait for two minutes. Use the adjusng switch to
erase the two set end posions. Set the end posions again.
Cause 2 Possibly the electronics are defecve.
Soluon 2 Contact your supplier or the manufacturer.
9.2 Technical support
For technical support contact your local Aer Sales contact person. You can nd your local Aer
Sales contact person on our website at www.ridder.com.