Rockwell Automation Publication D2-3518-4 - January 2020 109
Parameter Descriptions Chapter 9
Defines the analog input level that stops the drive. This parameter is not used 
with LiquiFlo 2.0 AC drives.
Defines the amount of time at or below Sleep Level before a stop command is 
issued. This parameter is not used with LiquiFlo 2.0 AC drives.
Sets the reaction to a loss of input power. If Power Loss Mode is set to:
Coast or Coast Input
• Rectifier can no longer synchronize to the AC line, or
• DC bus voltage is 
≤ 73% of its value at the time of the input power loss.
Decel, Decel Input, or Decel Fault
• Rectifier can no longer synchronize to the AC line, or
• DC bus voltage is 
≤ 82% of its value at the time of the input power loss.
Continue
• Rectifier can no longer synchronize to the AC line, or
• DC bus voltage is 
≤ 305V DC.
182
Sleep Level
Range: 4.000 mA, 0.000V / Wake Level   [0.001 mA, 0.001V]
Default: 5.000 mA, 5.000V
Access: 1  Path: Dynamic Control > Restart Modes
See also: 183
183
Sleep Time
Range: 0.0...30.0   [0.1 sec]
Default: 1.0
Access: 1  Path: Dynamic Control > Restart Modes
See also: 182
184
Power Loss Mode
Range: 0 = Coast
1 = Decel
2 = Continue
3 = Coast input (same as Coast in Liquiflo 2.0 drives)
4 = Decel input (same as Decel in Liquiflo 2.0 drives)
5 = Decel fault
Default: 0 = Coast
Access: 0 Path: Dynamic Control > Power Loss
See also: 185, 169, 190, 238, rectifier 64, rectifier 65