50 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 5 Installing Input and Output Power Wiring
Installing Wiring from the 
Power Module Output 
Terminals to the Motor 
Use the following steps to connect the AC output power wiring from the power 
module to the motor.
1. Turn off, lock out, and tag the input power to the drive. Wait 5 minutes.
2. Remove the input wiring panel and drill the required number of openings 
for the wiring. See Figure 14 on page 37
 and Figure 16 on page 39.
3. Connect the three-phase AC output power motor leads to the power 
module busbars labeled U, V, and W. See Figure 15 on page 38
 and 
Figure 17 on page 40
.
4. Tighten the three-phase AC output power terminals:
• Frame 3 – M10 Class 8.8 or 3/8 in. Grade 5 fastener. Tighten to 
40N•m (30 lb•ft).
• Frame 4 – M12 Class 8.8 or 1/2 in. Grade 5 fastener. Tighten to 
100N•m (75 lb•ft).
Table 5 - Recommended Minimum Motor Lead Wire Size
IMPORTANT The total motor lead length must not exceed 76 m (250 ft). See Table 5 for 
recommended minimum motor lead wire sizes.
Power Module Model Number  Minimum Motor Lead Wire Size
(1)
(1) Motor lead wiring must comply with all local and national codes.
LF200460AAR  2 x 2/0 AWG
LF200608CCR  2 x 250 MCM
LF200900CCR 4 x 250 MCM 
LF201215CCR  4 x 250 MCM